White Arch Company KSA
HomeAbout
Solutions
MarketsStandardsContactBlog
Request proposal
← Blog
Engineering guide

Circuit Breaker Types Explained: MCB, MCCB, ACB, RCCB and RCBO for Commercial Buildings

Afzal Basheer, General Manager·Nov 10, 2026·Updated Nov 16, 2026·10 min read
Circuit Breaker Types Explained: MCB, MCCB, ACB, RCCB and RCBO for Commercial Buildings
Quick answer

The main circuit breaker types used in commercial buildings are the MCB (miniature circuit breaker), MCCB (molded case circuit breaker), ACB (air circuit breaker), RCCB (residual current circuit breaker) and RCBO (residual current breaker with overcurrent). MCBs, MCCBs and ACBs protect against overload and short circuit at rising current ratings and breaking capacities, from final circuits up to the main low voltage incomer. RCCBs and RCBOs add earth leakage protection, with the RCBO combining overcurrent and residual current protection in one device. The correct selection follows from the prospective short circuit current, the load and the earthing system, not from brand.

The main circuit breaker types in a commercial installation

Circuit breaker types are classified by their construction, current rating, interrupting (breaking) capacity and the kind of fault they protect against. In a commercial building the circuit breaker types most engineers specify are the MCB, MCCB, ACB, RCCB and RCBO, each sitting at a different point in the distribution system from the final circuit up to the main low voltage panel. Choosing between these circuit breaker types is not a matter of brand preference: it follows from the prospective short circuit current at the board, the connected load, the earthing arrangement and the level of personnel and fire protection the application demands. White Arch specifies, installs and tests all five circuit breaker types on commercial and industrial electrical and MEP distribution boards across Saudi Arabia.

The circuit breaker types covered in this guide split cleanly by function. MCBs, MCCBs and ACBs are overcurrent devices that protect conductors and equipment from overload and short circuit, while RCCBs and RCBOs add residual current, or earth leakage, protection to guard people and reduce fire risk. Reading each of the circuit breaker types against its product standard, current rating and breaking capacity is the fastest way to select the right device for each position on a board. The sections below define each device, compare them in a single table and give a practical selection guide for commercial and industrial boards, drawing on the low voltage power and distribution scope White Arch delivers.

What each device does

MCB: miniature circuit breaker

The MCB is the smallest overcurrent device, built to IEC 60898-1 for household and similar fixed installations, and to IEC 60947-2 when used in industrial switchgear. It protects final circuits such as lighting, small power and socket outlets against overload and short circuit using a thermal element for slow overloads and a magnetic element for fast short circuits. MCBs are selected by trip curve: type B trips at roughly three to five times rated current for resistive and lighting loads, type C at five to ten times for mixed and small motor loads, and type D at ten to twenty times for high inrush equipment such as transformers.

MCCB: molded case circuit breaker

The MCCB is a larger overcurrent device built to IEC 60947-2, housed in a molded insulating case, and used for sub-main feeders, motor circuits and distribution boards where the current rating or fault level exceeds what an MCB can handle. Many MCCBs offer adjustable thermal and magnetic settings, and larger frames carry electronic trip units with adjustable long-time, short-time, instantaneous and sometimes ground-fault protection. This adjustability lets an engineer grade an MCCB against upstream and downstream devices for discrimination.

ACB: air circuit breaker

The ACB is the largest low voltage device, also built to IEC 60947-2, used at the main incomer of a main distribution board, on bus-tie positions and on large feeders. Air circuit breakers are usually withdrawable for maintenance, carry advanced electronic trip and metering units, and provide the high breaking capacity and short-time withstand that a main low voltage panel needs. Their adjustable protection and communication features make them central to the main switchboard and to power management.

RCCB and RCBO: earth leakage protection

An RCCB (residual current circuit breaker), built to IEC 61008-1, detects the small residual current that flows to earth during an insulation fault or contact with a live part, and disconnects the circuit. It does not provide overload or short circuit protection on its own, so it must be installed in series with an MCB or fuse. An RCBO (residual current breaker with overcurrent), built to IEC 61009-1, combines the functions of an RCCB and an MCB in a single device, giving overload, short circuit and earth leakage protection on one final circuit. Residual devices are specified by sensitivity, commonly 30 mA for personnel protection and 100 or 300 mA for fire protection, and by type (AC, A, F or B) according to the waveform of the leakage current the load can produce.

Electrical room with a long lineup of low voltage switchgear panels, yellow and black floor markings and an engineer
A row of low voltage switchgear panels where air circuit breakers and molded case breakers sit on the main distribution board.
Reviewing the breaker schedule for a commercial board?
Share your scope and drawings and White Arch will respond with a technical proposal.
Request proposalWhatsApp +966 57 048 3020

Circuit breaker types compared

The table below compares the five circuit breaker types by rating, typical breaking capacity and typical use. Breaking capacity is the highest fault current a device can interrupt safely; under IEC 60947-2 it is stated as the rated ultimate value (Icu) and the rated service value (Ics), while IEC 60898-1 states it as Icn. All values are indicative and must be confirmed against the manufacturer data and the project short circuit study.

Device Standard Typical current rating Typical breaking capacity Typical use
MCB IEC 60898-1 Up to about 125 A About 6 to 10 kA (Icn) Final circuits: lighting, small power, socket outlets
MCCB IEC 60947-2 About 16 to 1600 A (frames to 3200 A) About 16 to 100 kA (Icu) Sub-main feeders, motor and large loads, sub distribution boards
ACB IEC 60947-2 About 630 to 6300 A About 50 to 150 kA (Icu) Main low voltage incomer, bus-tie, large feeders
RCCB IEC 61008-1 Up to about 125 A Requires backup overcurrent device Earth leakage protection in series with an MCB or fuse
RCBO IEC 61009-1 Up to about 125 A (commonly 63 A or less) About 6 to 10 kA Final circuits needing overcurrent and earth leakage in one device

The pattern across the circuit breaker types is consistent: current rating and breaking capacity rise from the MCB on a final circuit, through the MCCB on feeders, to the ACB at the main incomer, while the RCCB and RCBO handle the separate job of earth leakage.

RCCB vs RCBO and MCCB vs MCB

Two comparisons come up on almost every commercial board. RCCB vs RCBO is a question of integration: an RCCB protects a group of circuits against earth leakage from one point but gives no overcurrent protection, so a fault on any circuit in the group trips the whole group. An RCBO protects a single final circuit with both overcurrent and earth leakage, so a fault isolates only that circuit, which improves continuity of supply in occupied buildings. The trade is more devices and board space against better selectivity.

MCCB vs MCB is a question of scale and adjustability. An MCB is fixed, compact and suited to final circuits up to about 125 A at modest fault levels. An MCCB handles higher currents and fault levels and, crucially, offers adjustable settings that let an engineer coordinate it with upstream and downstream devices. Where fault levels are high, as they often are close to a large transformer, an MCCB or ACB with an adequate Icu is required and an MCB alone is not suitable. ACB vs MCCB then follows the same logic at the top of the board: the ACB is chosen at the main incomer for its higher breaking capacity, short-time withstand and withdrawable maintenance.

Electrician in hi vis testing circuit breakers inside an open distribution board
An electrician tests circuit breakers inside an open distribution board during commissioning.

Selection guide for commercial and industrial boards

Selecting devices for a distribution board is a top-down exercise that starts from the short circuit study and the single line diagram. The steps below set out how White Arch approaches a commercial or industrial board.

  1. Establish the fault levels. Calculate the prospective short circuit current at each board from the transformer and upstream impedance. Every device must have a rated breaking capacity (Icu, or Icn for an MCB) at or above the fault level at its position.
  2. Size the main incomer. At the main low voltage panel select an ACB, or a large MCCB on smaller boards, rated for the full load current with an electronic trip unit for adjustable protection and metering.
  3. Select the feeders. For sub-main feeders and motor circuits choose MCCBs rated for the load, with settings that can be graded against the incomer and the final devices for discrimination.
  4. Specify the final circuits. Use MCBs with the correct trip curve (B, C or D) for the load, or RCBOs where earth leakage protection is required on individual circuits.
  5. Add residual current protection. Apply 30 mA devices for socket outlets and personnel protection and 100 or 300 mA devices for fire protection on larger feeders, choosing the RCD type (A, F or B) to suit electronic loads and drives.
  6. Verify coordination. Confirm discrimination between series devices and, where required, back-up protection (cascading) so that an upstream device supports a downstream one at high fault current.

Distribution board types follow this hierarchy: the main distribution board or main low voltage panel at the incomer, sub-main distribution boards for zones or risers, and final distribution boards close to the loads. Matching the circuit breaker types to the right board position, and documenting the result in a tested breaker schedule, is part of the handover White Arch provides on turnkey electromechanical projects. Device standards referenced here are published by the IEC.

Written by Afzal Basheer, General Manager, White Arch. White Arch delivers turnkey HVAC, MEP, electrical and specialist live-line services across Saudi Arabia, with regional electromechanical experience since 2008. About White Arch · Standards
Talk to White Arch about low voltage distribution and switchgear
Request a proposal, send drawings for review or message the team on WhatsApp. Email info@whitearch.sa.
Request proposalWhatsApp +966 57 048 3020

Frequently asked questions

What are the main circuit breaker types used in commercial buildings?
The main circuit breaker types are the MCB, MCCB and ACB for overcurrent protection and the RCCB and RCBO for earth leakage protection, arranged from final circuits up to the main low voltage incomer.
What is the difference between an MCB and an MCCB?
An MCB is a compact fixed device for final circuits up to about 125 A at modest fault levels, while an MCCB handles higher currents and fault levels and offers adjustable trip settings for coordination on feeders and sub-main boards.
What is the difference between an RCCB and an RCBO?
An RCCB provides earth leakage protection only and must be paired with an MCB or fuse, while an RCBO combines earth leakage and overcurrent protection in one device, so a fault isolates a single circuit instead of a whole group.
When is an ACB used instead of an MCCB?
An ACB is used at the main incomer, bus-tie and large feeders of a main distribution board where very high current ratings, high breaking capacity and a withdrawable, maintainable design are needed, whereas an MCCB covers lower feeder ratings.
What is breaking capacity and why does it matter?
Breaking capacity is the highest fault current a device can interrupt safely, stated as Icu and Ics under IEC 60947-2 or Icn under IEC 60898-1; a device with a breaking capacity below the fault level at its position can fail dangerously during a short circuit.
What residual current sensitivity should be specified?
A 30 mA sensitivity is used for personnel protection on socket outlets and similar circuits, while 100 or 300 mA devices are used for fire protection on larger feeders, with the RCD type chosen to suit the leakage waveform of the connected loads.

Back to All Articles
White Arch Company KSA

Regional engineering experience since 2008. Delivering integrated HVAC, MEP and specialist solutions across Saudi Arabia.

Request proposal

→
Hours
By consultation · 24/7 critical response
Areas served
Dammam · Eastern Province (HQ)Riyadh · Central RegionWestern ProvinceKingdom-wide

Explore

AboutServicesSolutionsMarketsStandardsContact

© 2026 White Arch Company. All rights reserved.

Engineering today. A stronger tomorrow.
Made and managed by 🎁 Storebox